The GE Infinity M DC energy system is a modular power plant that supports dual voltage
(+24V/-48V) operation through the use of a comprehensive range of advanced rectifiers and
DC-DC converters. Primary voltage is supported by rectifiers and battery reserve, while secondary
voltage is supported by DC-DC converter modules. Primary voltage can be -48V or +24V.
The Infinity M Power System has primary voltage capacity for +24V and -48V power up to
1,600A; secondary voltage capacity is up to 600A per expansion module.
Shelf / Bay Options
Infinity M systems may be equipped in
a 7ft 23” relay rack; a half height rack
for mounting on battery stands; indoor
or outdoor power cabinets; or mounting
rails for field install applications. The
distribution module is 14U (24.5”) tall and
accommodates up to 80 single voltage or
selectable voltage bullet breaker positions.
Universal shelves are 1U tall with four slots
that accept any Infinity series rectifier or
converter interchangeably in any power
slot. This allows the available slots to be
filled with the mix of power modules desired.
The only restriction is whether AC power
is applied to the shelf. This gives extreme
flexibility in the provisioning of power
modules within the system.
Infinity Rectifier and
Converter Family
The Infinity Series offers DC rectifiers and
converters for both +24V to -48V and -48V to
+24V applications. For easy module selection,
the rectifiers and converters are color coded
to quickly identify voltage, module type and
input voltage type (AC or DC).
Galaxy Pulsar* Plus Controller
The Galaxy Pulsar Plus is used throughout
many of the GE DC Power products
including Infinity, CP, and SPS with the
only differentiator being the form factor
which is scaled to meet the nature of the
application. The controller utilizes standard
network management protocols allowing
for advanced network supervision with
SNMP communications to deliver extensive
monitoring and control features with both
local and remote access.
Features and Benefits
Reliability
• Distributed fault tolerance
• Proven field performance
• Controller continuity
Intelligence
• Industry leading controller features
• Ethernet interface for remote access
• Centralized network management
Investment Protection
• Module Compatibility
• Power Shelf Growth
• Secondary Voltage flexibility +24V / -48V
• Flexible Upgrade Options
Infinity M Power System
Dual Voltage, Rack Mounted Power System
• ECO Priority Source*
Ready
• DualVoltagepower
system with
ultimate flexibility
• -48Vupto1,600A
(86KW) or +24V up to
1,600A (44KW)
• SecondaryVoltageLoad
capacity up to 600A
• Highavailability
wireless telecom
applications
• Telecomservice
providers
• Efciency
approaching 97%
Vue de la page 0
1 2 3 4 5 6 ... 19 20

Résumé du contenu

Page 1 - Infinity M Power System

The GE Infinity M DC energy system is a modular power plant that supports dual voltage (+24V/-48V) operation through the use of a comprehensive range

Page 2 - Specifications

GECriticalPower.com10+24V Primary Voltage Systems with -48V Converters Output Ordering Code Model Frame PictureCC109141974 1,200A (1,600A max) 24V s

Page 3

GECriticalPower.com11RectifiersOrdering Code Model PhotoCC109160834 95 - 145Vac input, 24V, 44A output (max. 50A@24V)175 - 275Vac input, 24V, 100A outp

Page 4 - Pulsar Plus Controller

GECriticalPower.com12Step4:SelectDistributionComponentsBullet Style Load Circuit BreakersOrdering Code Amperage CB Positions (Poles) Min Wire Gaug

Page 5 - Galaxy Manager Compatible

GECriticalPower.com13Bullet Style Fuse Holder and TPS FusesOrdering Code Amperage WP-92461 List Min Wire Gauge Photo406700567 3 100 10406700583 5 101

Page 6 - Infinity M System

GECriticalPower.com14Step4:SelectDistributionComponents(cont.)Bullet Style GMT Fuse Holder and GMT FusesOrdering Code Amperage WP-92461 List Min

Page 7

GECriticalPower.com15Ordering Code Description PhotoModules # Inputs # Temp108469461 J85501G1L21RPMShuntMonitoring(221F) 6 1108469479 J85501G1L22

Page 8 - Ordering Guide

GECriticalPower.com16Step6:SelectBatteryMonitoringOrdering Code Description PhotoCC109142980 QS873A Thermal Probe (A)150026698 QS873B Ambient The

Page 9 - -48V Primary Voltage Systems

GECriticalPower.com17Notes

Page 10

GECriticalPower.com18Notes

Page 12 - GECriticalPower.com

Infinity Rectifiers and ConvertersApplicationsKey FeaturesSpecifications• Compact – 1RU form factor providing high power density (24 W/in3)• Dual Vo

Page 13

CPB-NEM, Rev. 9/13 *Trademark of General Electric Company. Copyright 2013 General Electric Company. All Rights Reserved. GE reserves the right to ma

Page 14

GECriticalPower.com3Outline DrawingEnvironmentalOperating Temperature -40°C to +75°C (-40°F to 167°F) Full capacity up to 55°C; output derates 2%/°C f

Page 15

Pulsar Plus ControllerApplicationsKey FeaturesThe Pulsar Plus family of controllers provides system monitoring and control features for Infinity, CP,

Page 16 - Temperature Measurement

GECriticalPower.com5Integrated Monitoring Inputs/Outputs• System plant voltage (accuracy ±0.5%, resolution 0.01V)• One system shunt (accuracy ± 0.5%

Page 17

GECriticalPower.com6Infinity M SystemApplicationsKey FeaturesSpecificationsInfinity M may be configured as a +24V or -48V single voltage power system

Page 18

GECriticalPower.com7Outline Drawing (for visual reference only)EnvironmentalOperating Temperature -40°C to +75°C (-40°F to 167°F) Storage Temperature

Page 19

GECriticalPower.com8Ordering GuideFeaturesInfinity M may be configured as a +24V or -48V single voltage power system or as a “dual voltage” power syst

Page 20 - CPB-NEM, Rev. 9/13

GECriticalPower.com9-48V Primary Voltage Systems Output Ordering Code Model Frame Picture-48VCC109152220 800A -48V single voltage system, includes 65

Commentaires sur ces manuels

Pas de commentaire